OPERATOR INSTRUCTIONS

STEP 1: Confirm that circuit breaker (14CB) is switched ON and CONTROL POWER pushbutton light (1PL) is lit.

  • If not, check phase monitor relay (PMR) and emergency stop (ES) button.
  • If INCORRECT POWER 1 pushbutton light (2PL) is lit, check PMR1 for phase rotation and voltage setting.

STEP 2: Turn ON FLOW switch (1SW).

STEP 3: Turn PUMP switch (2SW) to require pump operating mode.

  • VFD RUNNING pushbutton light (13PL) lit if pump is started using VFD.
  • BYPASS RUNNING pushbutton light (12PL) lit if pump is started using bypass starter.
  • Check pump overload (9OL) or VFD status if PUMP TRIP pushbutton light (14PL) is  lit.

STEP 3: Check DPS if NO FLOW pushbutton light (15PL) is lit.

STEP 4: Cooling probe selection switch (3SW).

  • Turn 3SW to LVG – Cooling is based on leaving temperature control.
  • Turn 3SW to RTN – Cooling is based on return temperature control.

STEP 5: Turn ON COMPRESSOR switch (6SW, 7SW, 8SW & 9SW).

STEP 6: Turn ON COOLING switch (5SW).

  • If INCORRECT POWER 2 pushbutton light (3PL) is lit, check PMR2 for phase rotation and voltage setting

STEP 7: Turn BYP/VFD switch (10SW, 11SW, 12SW & 13SW) to require condenser fan operating mode.

  • BYP – Condenser fan is started using bypass starter.
  • VFD – Condenser fan is started using VFD.

It is the customer’s responsibility to always follow the written operating instructions of the unit and maintain safe work practices.