START-UP FOR SMART FAMILY 25 TON INDUSTRIAL AC UNIT

OPERATOR INSTRUCTIONS

STEP 1: Confirm that circuit breaker (10CB) is switched ON and CONTROL POWER pushbutton light (1PL)
is lit.
• If not, check phase monitor relay (PMR) and emergency stop (ES) button.
• If INCORRECT POWER pushbutton light (2PL) is lit, check PMR for phase rotation and voltage
setting.

STEP 2: Turn ON AIR FLOW switch (1SW).

STEP 3: Turn BLOWER switch (2SW) to require blower operating mode.
• HAND – Blower is operating in manual mode without the controller (manual on).
• TSTAT – Blower is operating with local controller.

STEP 4: Turn BLOWER switch (8SW) to require blower operating mode.
• VFD RUNNING pushbutton light (3PL) lit if blower is started using VFD.
• BYPASS RUNNING pushbutton light (5PL) lit if blower is started using bypass starter.
• Check blower circuit breaker overload (5OL) or VFD status if BLOWER TRIP pushbutton light (4PL)
is lit.

STEP 5: Set blower running speed using SPD ADJ POT (potentiometer)

STEP 6: Turn HTG-CLG/DH-MODE STAT switch (5SW) to require controller operating mode.
• STAT HTG-CLG – AI1 (Logic mode) will be enabled.
• DH MODE – AI2 (DH mode) will be enabled.

STEP 7: Turn OFF/LOCAL/HAND/REMOTE switch (3SW, 4SW) to require compressor operating mode.
• OFF – Compressor is switched off.
• LOCAL – Compressor is operating with local controller.
• HAND – Compressor is operating in manual mode without the controller (manual on).
• REMOTE – Compressor is operating in remote mode without the controller (on/off by remote
thermostat)

STEP 8: Turn OFF/LOCAL/HAND/REMOTE switch (6SW) to require heater 1 operating mode.
• OFF – Heater 1 is switched off.
• LOCAL – Heater 1 is operating with local controller.
• HAND – Heater 1 is operating in manual mode without the controller (manual on).
• REMOTE – Heater 1 is operating in remote mode without the controller (on/off by remote
thermostat)

STEP 9: Turn OFF/LOCAL switch (7SW) to require heater 2 operating mode.
• OFF – Heater 2 is switched off.
• controller.

It is the customer’s responsibility to always follow the written operating instructions of the unit and maintain safe work practices.