This particular video demonstrates the start-up of our 50+ ton Industrial Air Handling Unit (SMTAH1D051Q). We appreciate you taking the time to watch and we hope this is a helpful tool for your team.

Start-up for 50+ Ton Industrial Air Handling Unit

OPERATOR INSTRUCTIONS

STEP 1: Confirm that circuit breaker (3CB) and Control Switch (5SW) are switched ON and CONTROL
POWER pushbutton light (1PL) is lit.
• If not, check phase monitor relay (PMR) and emergency stop (ES) button.
• If INCORRECT POWER pushbutton light (2PL) is lit, check PMR for phase rotation and voltage
setting.

STEP 2: Turn ON AIR FLOW switch (1SW).

STEP 3: Turn BLOWER switch (2SW) to require blower operating mode.
• VFD RUNNING pushbutton light (3PL) lit if blower is started using VFD.
• BYPASS RUNNING pushbutton light (5PL) lit if blower is started using bypass starter.
• Check blower circuit breaker overload (1OL) or VFD status if BLOWER TRIP pushbutton light (4PL)
is lit.

STEP 4: Set blower running speed using SPD ADJ POT (potentiometer)

It is the customer’s responsibility to always follow the written operating instructions of the unit and maintain safe work practices.