START-UP FOR SMART FAMILY 70 TON INDUSTRIAL AIR COOLED CHILLER

OPERATOR INSTRUCTIONS

STEP 1: Confirm that circuit breaker (8CB) is switched ON and CONTROL POWER pushbutton light (1PL)
is lit.
• If not, check phase monitor relay (PMR) and emergency stop (ES) button.
• If INCORRECT POWER pushbutton light (2PL) is lit, check PMR for phase
rotation and voltage setting.

STEP 2: Turn ON FLOW switch (1SW).

STEP 3: Check flow setting if NO FLOW pushbutton light (3PL) is lit.

STEP 4: Cooling probe selection switch (2SW)
• Turn 2SW to LVG – Cooling is based on leaving temperature control.
• Turn 2SW to ENT – Cooling is based on entering temperature control.

STEP 5: Turn ON COMPRESSOR switch (6SW and 7SW)

STEP 6: Turn ON COOLING switch (5SW)

STEP 7: Turn BYP/VFD switch (3SW & 4SW) to require condenser fan operating mode.
• BYP – Condenser fan is started using bypass starter.
• VFD – Condenser fan is started using VFD.
It

It is the customer’s responsibility to always follow the written operating instructions of the unit and maintain safe work practices.