This article provides guidelines on whether, where, and when to install a line-load reactor on an AC drive and what size reactor to use. Explore the ins and outs of line reactors for process cooling and the reasons for using them.
A line reactor is an inductor. It is a coil of wire that allows a magnetic field to form around it when current flows through it. When energized, it is an electric magnet, with the strength of the field proportional to the amperage flowing and the number of turns.
A simple loop of wire is an air core inductor. More loops give a higher inductance rating. Quite often, some ferrous material, such as iron, is added as a core to the winding. This concentrates the lines of magnetic flux, making a more effective inductor.
Going back to basic AC circuit theory, an inductor stores energy in the magnetic field and is resistant to a change in current. A reactor’s main property is its inductance, measured in Henrys, Millihenrys, or Microhenrys.
In a DC circuit (such as the DC bus in an AC drive), an inductor limits the current rate of change since the current in an inductor wants to continue to flow at the given rate for any instant. That is to say, an instantaneous increase or decrease in applied voltage will result in a slow increase or decrease in current.
Conversely, if the current rate in the inductor changes, a corresponding voltage will be induced. If we look at the equation V=L (di/dt) for an inductor where V is voltage, L is inductance, and (di/dt) is the rate of change of current in amps per second, we can see that a positive rise in current will cause a voltage to be induced.
Equating the Reactance of an Inductor
This induced voltage is opposite in polarity to the applied voltage and proportional to both the rate of rise of current and the inductance value. This induced voltage subtracts from the applied voltage, thereby limiting the rate of current rise. This inductance value is a determining factor of the reactance. The reactance is part of the total impedance for an AC circuit. The equation for the reactance of an inductor is XL = 2¶FL. Where XL is inductive reactance in Ohms, F is the applied frequency of the AC source and L is the inductance value of the reactor.
As you can see, the reactance and, therefore, the impedance of the reactor is higher with a higher inductance value. Also, a given inductance value will have a higher impedance at higher frequencies. Thus, we can say that in addition to limiting the rate of rise in current, a reactor adds impedance to an AC circuit proportional to both its inductance value and the applied frequency.
Therefore, a line reactor is often appropriate for adding line impedance.
Impact of a Line Reactor on Process Cooling Applications
Just as medicines with positive effects also have side effects, there are impacts of using a line reactor that may be beyond the scope of its intended purpose. Though these issues should not prevent the use of a reactor when required, the user should be aware of and ready to accommodate these effects.
Increased Heat and Losses
Since a reactor is made of wire (usually copper) wound in a coil, it will have the associated losses due to wire resistance. Also, if it is an iron core inductor (as in the case of most reactors used in power electronics), it will have some “eddy current” loss in the core due to the changing magnetic field and the magnetically realigned iron molecules. Generally, a reactor will add cost and weight, require space, generate heat and reduce efficiency.
Equipment Interference
Sometimes adding a line reactor can change the characteristics of your connected line.
Other components, such as power factor correction capacitors and stray cable capacitance, can interact with a line reactor, causing a resonance to be set up. AC drives exhibit a relatively good power factor and do not require correction capacitors. Power factor correction capacitors often do more harm than good where AC drives are present.
For the most part, power factor correction capacitors should never be used with a drive. You may find that adding a reactor completes the required components for a line resonance where none previously existed — especially where power factor correction capacitors are present. In such cases, either the capacitor or the inductor must be removed.
Voltage Drop
Furthermore, reactors have the effect of dropping some voltage, reducing the available voltage to the motor and or input of the motor drive.
Why Use a Line Reactor for Process Cooling Applications?
With all these side effects, why use a reactor? There are good reasons to install a reactor under certain conditions. Let’s start with the input side of a drive.
1. Line Reactors at the Input to Reduce Harmonics
Most standard “six pulse” drives are nonlinear loads. They tend to draw current only at the plus and minus peaks of the line. Since the current wave-form is not sinusoidal the current is said to contain “harmonics”. For a standard 3 phase input converter (used to convert AC to DC) using six SCRs or six diodes and a filter capacitor bank, as shown in Figure 1a below, the three-phase input current may contain as much as 85% or more total harmonic distortion.
Click to enlarge the image – Notice the high peaks.
If a line reactor is installed as in Figure 1b, the peaks of the line current are reduced and broadened out. This makes the current slightly more sinusoidal, lowering the harmonic level to around 35% when a properly sized reactor is used. This effect is also beneficial to the DC filter capacitors. Since the “ripple current” is reduced, the capacitors can be smaller, run cooler and last longer.
Though harmonic mitigation is an important reason to use a line reactor, most drives at the 10-horsepower rating and above include a “DC link choke,” as seen in Figure 1c. The link choke is a reactor put in the DC bus between the Rectifier bridge and the capacitor bank. It can provide the necessary harmonic mitigation, and since it is in the DC bus, it can be made smaller and cheaper than the 3-phase input reactor.
So, to conclude, a line reactor can be very useful in reducing harmonics. However, it’s important to remember that this is only true when no link choke is present.
2. Small Drives May Need an Input Reactor
Generally, drives less than 10 HP do not have a DC link reactor. That’s not a problem in most cases since any harmonic current distortion would be small compared to the facility’s total load. If many small drives are required for a process, an input reactor is a valid method for reducing harmonics.
In these cases, it is often more economical and practical to connect a group of 5 to 10 drives through one large three-phase reactor, as shown in Figure 2.
The best scenario for installing an input reactor is probably when you have a small drive where the transformer feeding the drive may be 20 times the current or power rating of the drive or greater. In some cases, a large transformer (one with a low source impedance and or high short circuit capability) feeding a relatively small drive can result in overheating of the drive’s internal DC capacitor bank.
When an NTC (negative temperature coefficient) pre-charge system is used, a large transformer feeding the drive can result in excessive inrush, clear line fuses, or damage to the drive. An input line reactor here will help. In this case, the reactor reduces harmonic current, but the real reason for its presence is to limit the peak current that will flow at the input and in the capacitor bank.
3. Line Reactors as Line Voltage Buffers
In some cases, other switch gear on the line, such as contactors and disconnects, can cause line transients, particularly when inductive loads such as motors are switched off. In such cases, a voltage spike may occur at the drive’s input, which could result in a surge of current at the input. If the voltage is high enough, a failure of the semiconductors in the DC converter may also result.
Figure 3Sometimes a reactor is used to “buffer from the line.” While a DC link choke, if present, will protect against a current surge, it cannot protect the converter from a voltage spike since a link choke is located after the converter (refer to Figure 1c). The semiconductors are exposed to whatever line voltage condition exists. For this reason, a reactor at the input to the drive may be of some help, but a better solution would be to attenuate the voltage spike at the source with a snubber circuit. Figure 3 shows both methods being used to protect the drive input semiconductors.
A reactor does not fix grounding issues or provide isolation. While it provides some buffering, it does not provide isolation and cannot replace an isolation transformer. If isolation is needed, an isolation transformer must be used. Contact your distributor for an appropriately sized transformer.
Also, it is important to note that while a reactor can provide light buffering from a short-duration (less than 1 ms) transient condition, it will not fix a high-line condition or protect against line swells (high line for several line cycles). Nor should it be expected to protect against high-energy short-duration events such as lightning strikes.
So, as a guideline, if you need some light buffering against low-magnitude line spikes, a line reactor can certainly help. However, it will not protect against high-energy, short-duration events.
4. Line Reactors at the Drive Output to Increase Load Inductance
Sometimes, applying a reactor to the output of a drive is necessary. Again, all the “side effects,” as previously stated, hold true. And yes, there are a few instances when adding load impedance by inserting an output reactor may be necessary. If the motor has a “low-leakage inductance,” a reactor can help bring the total load inductance back up to a level the drive can handle.
In the days of the “Bipolar transistor” drive, carrier frequencies rarely exceeded 1.5Khz. This meant that the transistor’s “on time” was much longer. This allowed current to ramp up higher, limited by the load or motor inductance. A low-inductance motor resulted in a huge ripple current that sometimes ran into the drive’s current limit, causing poor performance or tripping.
For the most part, the higher carrier frequencies and correspondingly lower ripple current of today’s IGBT (Isolated Gate Bipolar Transistor) drives have eliminated the need to add inductance to the load. Refer to the comparison in Figure 4.
In rare cases, in which a motor configuration is strange or a motor has six or more poles, the motor inductance may be too low, and a reactor may be needed. Running multiple motors on one drive may also produce a low inductance load, requiring an output reactor.
5. Line Reactors at the Drive Output to Reduce the Effect of Reflected Wave
A reactor at the output of a drive is sometimes installed to prevent a reflected wave voltage spike when long motor leads are required. This is not always a good practice. Though the reactor will slope off the voltage rise time, providing some benefit, it is not likely to limit the peak voltage at the motor.
In some cases, a resonance can be set up between the cable capacitance and reactor that causes even higher voltages to be seen at the motor. In general, a motor terminator is a better solution. If a reactor is installed at the output, it is most likely part of a specially designed “reflected wave reduction” device with parallel damping resistors. If a reactor is used at the output, it should be located as close to the drive end as is possible.
Figure 5 shows the motor voltage before and after reactor installation. The DC bus voltage is shown for reference. Notice that the rise times are different. The peak voltage is about twice the DC bus voltage regardless of whether a reactor is used.
Since a current-regulated drive requires a “voltage margin” to regulate current, the output voltage is already limited by about 5%. Adding a reactor at the output will drop the voltage even further. A reactor at the output of this type of drive may not be a problem so long as the application can run without full motor voltage near full speed (typically 55 to 60 hertz). In some cases, a specially wound motor may be used to compensate. For example, a 460 volt 150 amp motor may be rewound as a 400 volt 175 amp motor.
Remember: You can use a reactor to filter reflected wave induction. However, do not expect this to limit the peak voltage at the motor.
Line Reactors vs. Line Filters
Line reactors and line filters serve a similar purpose — improving the electrical supply’s performance and quality. There are distinct differences, which we’ll explore below.
Line Reactor
We’ve determined the multiple uses of line reactors for process cooling applications, so we’ll discuss additional aspects that distinguish them from line filters. These include:
- Additional applications: This includes low-quality systems, systems concerning voltage spikes and extensive cable runs.
- Installation: The line reactor is between the VFD and the power supply.
- Purpose: Line reactors minimize current spikes and reduce harmonics to protect electronics.
- Harmonic mitigation: They improve system efficiency by reducing harmonics from the VFD.
Line Filter
The distinction with a line filter lies in reducing or completely eliminating electrical disturbances instead of reducing harmonics and current spikes. Consider the following:
- Additional applications: Line filters suit precision equipment and have controls sensitive to electrical disturbance.
- Installation: The line filter is also installed between the VFD or load and the power supply.
- Purpose: Line filters reduce the power supply’s electrical noise and harmonics.
- Harmonic mitigation: They decrease harmonics and electrical noise from the power supply to the VFD.
Sizing Line Reactors
The first rule is to ensure you have a high enough amp rating. Regarding the impedance value, 3% to 5% is the norm, with most falling closer to 3%. A 3% reactor is enough to provide line buffering, and a 5% reactor would be a better choice for harmonic mitigation if no link choke is present.
Output reactors, when used, are generally around 3%. This percentage rating is relative to the load or drive where the reactor impedance is a percentage of the drive impedance at full load. Thus, a reactor with a 3% concentration of applied voltage will drop 3% at a full-rated current.
Formula to Calculate Inductance Value
To calculate the actual inductance value, we would use the following formula: L = XL/(2¶FL), where L is inductance in Henrys, XL is inductive reactance or impedance in Ohms, and F is the frequency. Frequency will generally be the line frequency for both input and output reactors.
Your drive distributor should be able to help you size a reactor for use with a drive. If you wish to calculate the value yourself, the following example may be helpful. If a 3% reactor was required for a 100 amp 480 volt drive, a 100 amp or larger current rating would be required. The drive impedance would be Z=V/I or 480/100 = 4.8 ohms. 3% X 4.8 ohms = 0.114 ohms. Inserting this 0.114 impedance in the equation for inductance, we get a value of about 300 Microhenrys.
Line Reactors Summary
A reactor is not a magic wand or a silver bullet, but it can prevent certain problems when applied properly. You do not need a reactor at the input or output, but it can help provide some line buffering or add impedance, especially for drives with no DC link choke.
For small drives, reactors can prevent inrush or provide a reduction in current harmonics when many small drives are located at one installation. They should only be used to correct low motor inductance at the output, not as a motor protection device.
When to Use a Line Reactor
Knowing when to use a line reactor is vital because it manages harmonics and other electrical system components. Below, we’ve elaborated on some of its applications.
- To add line impedance: Long cable run systems benefit from a line reactor, which adds impedance and reduces voltage drop effects. It also helps promote system stabilization and improves the power system’s quality.
- To protect against voltage spikes: A line reactor buffers slightly against low-magnitude line spikes.
- To reduce harmonics: This is considerable when no link choke is present, such as smaller drives. It also reduces harmonics in devices with nonlinear loads, such as VFDs.
- To compensate for a low-inductance motor: A line reactor can increase the load inductance so the system is stable and doesn’t trip, impacting performance.
- To limit the impact of the inrush current: A powered device experiences an initial power surge that can damage the drive, especially a smaller one. Using a line reactor helps limit the inrush current to prevent the system from over-surging.
- As a filter for reflected wave reduction: A line reactor can help reduce the impact of reflected waves in long motor lead systems.
Contact Smart Family for More Information
To learn more about line reactors for process cooling and their impact on process cooling applications or get information on the Smart Family line of cooling products, contact us online now to discuss applications with a Smart Cooling representative.
Or, fill out a form to get an instant chiller quote!